Siemens Sirius 3RT2 Power Contactor 40 A · 4 Pole · 230 V AC · 1 NO + 1 NC · AC1 Duty · Size 0 · 3RT2326-1AP003RT2326-1AP00↓ 40% off1 / 2
BrandSiemens
CategoryIndustrial Control
SpecificationContactor · 3RT2
Brand SKU3RT2326-1AP00
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
Siemens· In stock
Visit the Siemens store

Siemens Sirius 3RT2 Power Contactor 40 A · 4 Pole · 230 V AC · 1 NO + 1 NC · AC1 Duty · Size 0 · 3RT2326-1AP00

$105.10/pc-40%
$175.16
Wholesale · 15+ units
$99.84 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$105.10 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $99.84/pc on this product, applied automatically

Siemens Sirius 3RT2 Power Contactor 40 A (article 3RT2326-1AP00) is a contactor from Siemens, 3RT2 series, sold by Elume with a GST invoice and pan-India delivery. Key data: manufacturer product name contactor AC-1, 40 A, 400 V / 40 °C, 4-pole, 230 V AC, 50 Hz, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S0, ampere/current rating 40 A, no. of poles 4 Pole, auxiliary contact 1 NO + 1 NC, coil voltage 230V AC, duty AC1 Duty, size Size S0. Priced at the Siemens India list price of 2026 (MRP before GST Rs 10,225), GST included in the price shown.

As published by Siemens. Verify critical parameters against the datasheet before specifying.
Siemens Siemens Sirius 3RT2 Power Contactor 40 A · 4 Pole · 230 V AC · 1 NO + 1 NC · AC1 Duty · Size 0 · 3RT2326-1AP00 · 3RT2326-1AP00
Device typeContactor
Series3RT2
Poles4P (FP)
Rated current40 A
Coil / control supply230 V AC
BrandSiemens
Brand SKU3RT2326-1AP00
ELINEGH2PGPFMJ
Sold asPer pc
DutyAC1 Duty
SizeSize S0
Coil Voltage230V AC
No. Of Poles4 Pole
Auxiliary Contact1 NO + 1 NC
Ampere/Current Rating40 A
Manufacturer Product Namecontactor AC-1, 40 A, 400 V / 40 °C, 4-pole, 230 V AC, 50 Hz, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S0
Ratings as published by Siemens (eleczo.com listing; Siemens spec table; Elume). Verify critical parameters against the datasheet before specifying.
How do I choose a contactor for my motor?

Select by the contactor's AC-3 current (or kW) rating at your supply voltage, which should be at least the motor's full-load current from the nameplate. Do not go by the higher AC-1 rating, which applies only to resistive loads (contactors are covered by IS/IEC 60947-4-1).

What is the difference between AC-1 and AC-3 rating?

AC-1 is for non-inductive or slightly inductive loads like heaters, while AC-3 is for starting and stopping squirrel cage motors. The same contactor has a much lower AC-3 rating than AC-1, and AC-4 (inching or plugging) is even more demanding.

Does a contactor protect the motor?

No. A contactor only switches the motor on and off; overload protection needs a thermal overload relay and short-circuit protection needs an MPCB, MCB, MCCB or fuses upstream.

Why is my contactor humming or chattering?

Common causes are low or fluctuating control voltage, a wrong coil voltage, dust or rust on the magnet faces, or a broken shading ring. Check the supply at the coil terminals first, then clean or replace the contactor if needed.

How many auxiliary contacts does this have and can I add more?

Most contactors have built-in auxiliary contacts (NO and/or NC) for holding and interlocking circuits, and many allow add-on auxiliary blocks on the front or side. Check the contact configuration and add-on compatibility in the product details.

How many contactors do I need for a star-delta starter?

A star-delta starter uses three contactors (main, delta and star), a star-delta timer and an overload relay. The main and delta contactors are typically sized at about 58% of the motor current and the star contactor smaller, as per the manufacturer's selection table.