Schneider Schneider Harmony XB5N Selector Switch · 22 mm · 2 NO · IP65 · XB5AD53N · XB5AD53N
Rated current3 A
Ingress protectionIP65
Reference standardIEC 60947-5-4
Net weight0.053 kg
BrandSchneider
Brand SKUXB5AD53N
ELINEGDCF7MHKF
Sold asPer pc
Depth70 mm
Width30 mm
Height42 mm
Head typeStandard
Fixing modeFixing nut recommended torque: 2.2 N.m (+/- 0.2 N.m)
Torque value0.14 N.m NO changing electrical state
Bezel materialDark grey plastic
Contacts usageStandard contacts
Device mountingFixing hole - diameter: 22.5 mm 22.3 +0.4/0 conforming to IEC 60947-5-1
Surge withstand1 kV conforming to IEC 61000-4-5
Operator profileBlack standard handle
Positive openingWithout
Range of productHarmony XB5N/XB7N
Type of operatorTo centre 3 spring return
Contact operationSlow-break
Contacts materialSilver alloy (Ag/Ni)
Device short nameXB5N
Mounting diameter22.5 mm
Tightening torque0.8…1.2 N.m conforming to IEC 60947-1
Device presentationComplete product
Shape of screw headCross compatible with Philips no 1 screwdriver · Cross compatible with pozidriv No 1 screwdriver · Slotted compatible with flat Ø 4 mm screwdriver · Slotted compatible with flat Ø 5.5 mm screwdriver
Overvoltage categoryClass II conforming to IEC 60536
Protective treatmentTH
Electrical durability1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C · 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C · 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C · 1000000 cycles, DC-13, 0.2 A at
Mechanical durability1000000 cycles
Product compatibilityZB5...N
Electrical reliabilityΛ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to IEC 60947-5-4 · Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to IEC 60947-5-4
Fixing collar materialPlastic
Connections - terminalsScrew clamp terminals, = 1 x 0.22 mm² without cable end conforming to IEC 60947-1
IK degree of protectionIK04 conforming to IEC 50102
Short-circuit protection10 A cartridge fuse type gG conforming to IEC 60947-5-1
Product or component typeSelector switch
Shape of signaling unit headRound
Contacts type and composition2 NO
Operator position information3 positions +/- 45°
Sale per indivisible quantity20
[Ui] rated insulation voltage600 V (pollution degree 3) conforming to IEC 60947-1
Terminals description ISO n°1(13-14)NO · (23-24)NO
[Ie] rated operational current3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1 · 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1 · 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1 · 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1 · 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1 · 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1
Electrical shock protection classClass II conforming to IEC 60536
Ambient air temperature for storage-40…70 °C
Ambient air temperature for operation-25…70 °C
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
[Ith] conventional free air thermal current10 A conforming to IEC 60947-5-1
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.