Schneider PowerLogic VPL6 Power Factor Controller · VarPlus Logic · VPL 6 · VPL06NVPL06N↓ 40% off
BrandSchneider
CategoryIndustrial Control
SpecificationVarPlus Logic · VPL 6
Brand SKUVPL06N
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
Schneider· In stock
Visit the Schneider store

Schneider PowerLogic VPL6 Power Factor Controller · VarPlus Logic · VPL 6 · VPL06N

$670.69/pc-40%
$1,117.83
Wholesale · 15+ units
$637.16 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$670.69 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $637.16/pc on this product, applied automatically

VarPlus logic is a simple and efficient Power Controller for a automatic power factor correction equipment to maintain the power factor. It is a simple and intelligent relay which measures,monitor and Controls the reactive energy. It comes with Easy Commisioning , Step Size detection and monitoring along with the variour alarms. VPL06 can be used for 6 steps in a PFC equippment

As published by Schneider. Verify critical parameters against the datasheet before specifying.
Schneider Schneider PowerLogic VPL6 Power Factor Controller · VarPlus Logic · VPL 6 · VPL06N · VPL06N
Ingress protectionFront face: IP41
Reference standardIEC 61000-6-2
Net weight0.6 kg
BrandSchneider
Brand SKUVPL06N
ELINEDG97FPJ24
Sold asPer pc
Depth58 mm
RangePowerLogic
Width144 mm
Height144 mm
StandardsIEC 61000-6-2 · EN 61010-1 · IEC 61000-6-4 · IEC 61326-1 · UL 61010-1
Input typeInsensitive to phase rotation polarity · Insensitive to CT polarity · Phase to neutral · Current input CT...X/5 A and X/1 A · Phase to phase
Colour codeFront: dark grey RAL 7016
Output typeControl relay: 0.2 A 110 V DC · Control relay: 1 A 48 V DC · Control relay: 2 A 400 V AC 50/60 Hz · Control relay: 1 A 24 V DC · Control relay: 5 A 250 V AC 50/60 Hz · Control relay: 5 A 120 V AC 50/60 Hz · Fan: 5 A 250 V AC 50/60 Hz · Fan: 1 A 48 V DC · Alarm relay: 5 A 250 V AC 50/60 Hz · Alarm relay: 1 A 48 V DC
Display size56 x 25 mm
Display typeBacklit LCD
Product namePowerLogic PFC Controller
Metering typePower factor and displacement PF (signed, four quadrant) · Total current harmonic distortion THD (I) · Power factor average over lifetime · Temperature maximum · Phase current I1, I2, I3 RMS on load · Active power P, P1, P2, P3 on load · Reactive power Q, Q1, Q2, Q3 on load · Apparent power S, S1, S2, S3 on load · Voltage U21, U32, U13, V1, V2, V3 on load
Mounting modeFlush-mounted
Data recording5 alarms
Input functionSwitch: 1 x dry contact
Operating modeManual or automatic
Type of alarmsStep power loss ( 6 A CT) / Action: message and alarm contact · Hunting (unstable regulation) / Action: message and alarm contact + step blocked · Low current ( 130 % I1) / Action: message and alarm contact + step switched off · Overtemperature (50 °C) / Action: message and alarm contact + step switched off · Overtemperature (30 °C) / Action: fan switch · Overvoltage (+/- 10 %) / Action: message a
Type of settingChoice of stepping programs: auto · Choice of stepping programs: LIFO · Choice of stepping programs: linear · Delay between 2 successive switch on the same step: 5...1200 s · Step configuration programming: auto · Step configuration programming: off · Step configuration programming: fixed · Target cos phi: 0.7 inductive...0.7 capacitive · Target cos phi: dual cos φ
Mounting supportPanel - thickness: 1…3 mm
Time delay range1...6500 s (on reconnection) · 1...6500 s (on response)
Device connectionCommunication protocol: Modbus interface: RS485
Device short nameVPL6
Mounting locationIn cabinet
Compatibility codeVPL 6
Cut-out dimensions138 x 138 mm
Function availableAutomatic detection · Advanced programming (expert) · Manual programming · Any step sequence · Automatic initialisation
Operating altitude<= 2000 m
Provided equipmentUser manual
Measurement current0…5 A
Measurement voltage90…550 V AC 50/60 Hz
Type of measurementAmbient temperature inside the cubicle · Tan φ · Individual voltage harmonic · Cos φ · Operating time · Power factor · Capacitor current overload Irms/I1
Measurement accuracyVoltage +/- 1 % · Current +/- 1 % · Frequency +/- 1 % · Energy (P,Q,S) +/- 2 % · Cos φ +/- 2 % · Total voltage harmonic distortion THD (U) +/- 2 % · Individual voltage harmonic +/- 3 % · Temperature +/- 3 °C
Information displayedNumber of switching cycles per step · Remaining step capacity in % · Individual step size in kVAr
Product certificationsEAC · NRTL · cNRTL · CE
IP degree of protectionFront face: IP41 · Rear face: IP20
Operational Hours alarm100000 h without maintenance
Settings operating modeManual · Automatic
Operational counter alarm65000 cycles without maintenance
Product or component typePower factor controller
[Us] rated supply voltage90...550 V AC · <= 999 kV AC with external VT
Maximum at the common terminal10 A
Number of step output contacts6
Ambient air temperature for operation-20…60 °C
Number of quadrant operation for generator application4
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.
Other Schneider ranges and models in this category, closest in price to this one.
No reviews yet