Schneider Schneider Harmony Plug-in Relay · 2 C/O · 5 A · 230 V AC coil · IP40 · RXG21P7 · RXG21P7
Rated current5 A
Ingress protectionIP40
Reference standardIEC 61810-1
coil voltage230 V AC
Net weight0.02 kg
BrandSchneider
Brand SKURXG21P7
ELINECHFDMKM34
Sold asPer pc
StandardsIEC 61810-1 · UL 508 · CSA C22.2 No 14
Relay typeInterface relay
Reset time20 ms
status LEDWithout
Series nameRXG series
Test levelsLevel A group mounting
Control typeLockable test button
Load current5 A at 250 V AC
Shape of pinFlat (faston type)
Operating rate<= 1800 cycles/hour under load · <= 18000 cycles/hour no-load
Operating time20 ms
Local signallingFlag
Pollution degree2
Range of productHarmony Electromechanical Relays
Removable legendWith
Contacts materialSilver alloy (AgSnO2In2O3)
Relative humidity10…85 %
Average resistance23500 Ohm at 23 °C +/- 15 %
Contact resistance100 mOhm
Device presentationComplete product
Dielectric strength1000 V AC between contacts with micro disconnection · 5000 V AC between coil and contact with reinforced insulation · 3000 V AC between poles with basic insulation · 1300 V AC terminals and case with basic insulation
Protection categoryRT I
Overvoltage categoryIII
Electrical durability100000 cycles for NO resistive load at 55 °C · 100000 cycles for NC resistive load at 55 °C
Insulation resistance1000 MOhm at 500 V DC
Mechanical durability10000000 cycles
Product certificationsUL · CSA · EAC · CE · DNV
IP degree of protectionIP40
Safety reliability dataB10d = 100000
Utilisation coefficient20 %
Maximum switching voltage250 V AC · 30 V DC
Product or component typePlug-in relay
Drop-out voltage threshold>= 0.3 Uc AC
Maximum switching capacity1250 VA
Minimum switching capacity50 mW at 10 mA, 5 V DC
Electrical insulation classClass F
[Uc] control circuit voltage230 V AC
Contacts type and composition2 C/O
[Ui] rated insulation voltage250 V conforming to IEC · 300 V conforming to CSA · 300 V conforming to UL
[Ie] rated operational current5 A at 30 V (DC) conforming to UL · 5 A at 30 V (DC) conforming to IEC · 5 A at 250 V (AC) conforming to UL · 5 A at 250 V (AC) conforming to IEC
Ambient air temperature for storage-40…85 °C
Ambient air temperature for operation-40…70 °C
[Uimp] rated impulse withstand voltage1200 V AC between contacts with micro disconnection · 6000 V between coil and contact with reinforced insulation · 1500 V between terminals and case with basic insulation · 4000 V between poles with basic insulation
[Ithe] conventional enclosed thermal current5 A at -40…55 °C
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.