Schneider Schneider Easy TeSys LAEN Auxiliary Contact Block · EasyPact TVS · 1 NO + 1 NC · LAEN11 · LAEN11
Ingress protectionIP20
Reference standardEN/IEC 60947-1
ColourGrey (RAL 7011)
Net weight0.035 kg
BrandSchneider
Brand SKULAEN11
ELINE9G2CRHJCC
Sold asPer pc
RangeEasy TeSys
StandardsEN/IEC 60947-1 · EN/IEC 60947-5-1 · GB/T 14048.1 · GB/T 14048.5 · EN/IEC 60335-1:Clause 30.2 · EN/IEC 60335-2-40:Annex JJ
Protection typeGG fuse 10 A
Non-overlap time1.5 ms on energisation no overlap between NC and NO contact · 1.5 ms on de-energisation no overlap between NC and NO contact
Range of productEasy TeSys Control
Device short nameLAEN
Mounting locationFront
Device applicationSignalling
Operating altitude3000 m without derating
Range compatibilityEasyPact EasyPact TVS LC1E
Protective treatmentTH conforming to IEC 60068
Insulation resistance> 10 MOhm
Mechanical durability10 Mcycles
Product certificationsCB Scheme · CCC · CE · EAC
Connections - terminalsControl circuit: screw clamp terminals 1 1 mm² - external diameter: 6 mm - cable stiffness: solid or flexible with cable end · Control circuit: screw clamp terminals 1 1 mm² - external diameter: 6 mm - cable stiffness: solid or flexible without cable end · Control circuit: screw clamp terminals 2 2.5 mm² - external diameter: 6 mm - cable stiffness: solid or flexible with cable end · Control circui
IP degree of protectionIP20 conforming to IEC 60529
Pole contact composition1 NO + 1 NC
Minimum switching current5 mA
Product or component typeAuxiliary contact block
minimum switching voltage17 V
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
Auxiliary contacts operationInstantaneous
Environmental characteristicStandard environment
[Ui] rated insulation voltage690 V - for control circuit conforming to IEC 60947-5-1
[Ue] rated operational voltage<= 690 V
Ambient air temperature for storage-60…80 °C
Ambient air temperature for operation-5…55 °C
[Icw] rated short-time withstand current100 A - 1 s · 120 A - 500 ms · 140 A - 100 ms
[Ith] conventional free air thermal current8 A (at 60 °C)
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.