Schneider Schneider EasyLogic EM7290 Smart Demand Controller · PowerLogic EM7290 · LCD · RS485 · 30002975
Rated current1 A
Ingress protectionIP51 front:
BrandSchneider
Brand SKU30002975
ELINE922RCPMPM
Sold asPer pc
DepthInside : 72 mm
RangeEasyLogic
Width96 mm
Height96 mm
SignalCurrent3 x · Voltage4 x
Display typeGraphic display terminal
Product nameEasyLogic EM7200
Metering typeActive, reactive, apparent energy (signed, four quadrant) · Demand power P, Q, S · Demand current I1, I2, I3 · Unbalance current · Unbalance voltage
Accuracy classClass 0.2 active power conforming to IEC 62052-11 · Class 0.2 active power conforming to IEC 62053-22 · Class 2 reactive energy conforming to IEC 62053-23
Display colourMonochrome
Output voltage22...26 V DC@8 mA
type of network3P · 3P + N
Pollution degree2
Device short nameEM7290
Network frequency50 Hz · 60 Hz
Number of outputs3 form C relay
Relative humidity0…95 %
Display resolution128 x 128 pixels
[In] rated current1 A · 5 A
Measurement current0.010…1.2 A · 0.050…6 A
Measurement voltage110…415 V AC nominal · 90…480 V AC without PTs
Type of measurementMeasurement cycle as true rms value · Total current harmonic distortion THD (I) per phase · Total voltage harmonic distortion THD (U) per phase · Individual harmonics up to the 15th per phase · Phase angle
Measurement accuracyVoltage 0.5 % · Current 0.5 % · Active power 0.2 % · Apparent power 0.2 % · Power factor 0.2 % · Reactive power 2 %
Measurement categoryCategory III
Communication of dataNet energy
Power quality analysistotal harmonic distortion
Product certificationsUL · CUL listed · C-Tick conforming to IEC 61010-1 · C-Tick conforming to UL 61010-1 · CE
IP degree of protectionIP51 front: · IP30 rear:
Tamperproof of settingsProtected by access code
Messages display capacity4 lines
Product or component typeSmart demand controller
[Us] rated supply voltage90...277 V AC · 120...300 V DC
Communication port supportRS485
Communication port protocolModbus RTU
Electrical insulation classDouble insulation
Frequency measurement range47.5…63 Hz
Electromagnetic compatibilityElectrostatic discharge conforming to IEC 61000-4-2 · Immunity to radiated fields conforming to IEC 61000-4-3 · Immunity to fast transients conforming to IEC 61000-4-4 · Surge withstand conforming to IEC 61000-4-5 · Immunity tests-conducted disturbances conforming to IEC 61000-4-6 · Immunity to magnetic fields conforming to IEC 61000-4-8 · Immunity to voltage dips conforming to IEC 61000-4-11 · Ra
Maximum power consumption in W4.5 W at 300 V (maximum)
Maximum power consumption in VA10 VA at 240 V on power supply · 0.2 VA current and voltage
Ambient air temperature for storage-25…70 °C
Ambient air temperature for operation-10…60 °C
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.