HRC fuse links, holders and bases from Lauritz Knudsen: cylindrical (HF), DIN (HN) and bolted (HG/HQ) types, 2 A to 800 A at 415 V AC.
gG fuses are general-purpose and protect against both overload and short circuit in cables and feeders, while aM fuses only give short-circuit protection and are used with motors together with an overload relay. HRC fuses are covered by IS/IEC 60269.
The base must match the fuse's type and size, such as DIN/NH sizes (000, 00, 1, 2, 3) with knife-blade contacts or bolted/BS-type fuses with offset or centre tags. Check the fuse's size and mounting type before choosing a base or fuse switch.
HRC fuses have very high breaking capacity (often 80kA to 120kA), are current-limiting and are compact and economical, so they are widely used for backup protection, transformer and capacitor feeders and in fuse switches. They need replacement after operation, unlike breakers.
Drives, UPS and rectifiers with semiconductors often need fast-acting semiconductor fuses (aR or gR) to protect the power electronics. Use the fuse type and rating recommended in the equipment manual.
Many HRC fuses have a striker or indicator that pops out when the fuse operates. Otherwise, check continuity with a multimeter after isolating the circuit, and find the cause before replacing it.