🚚 Free delivery over ₹4,000 pan-India · we also ship worldwide · Buying in bulk? Get a quote in 24 hours →
3UA5800-2DZ2↓ 40% off
BrandSiemens
CategoryIndustrial Control
SpecificationOverload relay · 3UA5
Brand SKU3UA5800-2DZ2
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
Siemens· In stock
Visit the Siemens store

Siemens Sirius 3UA58 Thermal Overload Relay · 20-32 A · Contactor mounting · Z2 for 3TF47 7 · 3UA5800-2DZ2

$167.32/pc-40%
$278.88
Wholesale · 15+ units
$158.97 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$167.32 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $158.97/pc on this product, applied automatically

Siemens Sirius 3UA5 Thermal Overload Relay 20 - 32 A (article 3UA5800-2DZ2) is a overload relay from Siemens, 3UA5 series, sold by Elume with a GST invoice and pan-India delivery. Key data: manufacturer product name Bimetal overload relay, overload range 20 - 32 A, mounting type Contactor Mounting, reset type Manual Reset, trip class Class 10, operating type Thermal. Priced at the Siemens India list price of 2026 (MRP before GST Rs 16,280), GST included in the price shown.

As published by Siemens. Verify critical parameters against the datasheet before specifying.
Siemens Siemens Sirius 3UA58 Thermal Overload Relay · 20-32 A · Contactor mounting · Z2 for 3TF47 7 · 3UA5800-2DZ2 · 3UA5800-2DZ2
Device typeOverload relay
Series3UA5
MountingContactor Mounting
BrandSiemens
Brand SKU3UA5800-2DZ2
ELINE63MH26FF2
Sold asPer pc
ResetManual (convertible to auto at site)
VersionZ2
Reset TypeManual Reset
Trip ClassClass 10
For use with3TF47 7 contactors
Mounting TypeContactor Mounting
Setting range20-32 A
Operating TypeThermal
Overload Range20 - 32 A
Manufacturer Product NameBimetal overload relay
Ratings as published by Siemens (eleczo.com listing; Elume). Verify critical parameters against the datasheet before specifying.
What should I set the overload relay to?

Set it to the motor's full-load current from the nameplate, not higher. In a star-delta starter where the relay is in the phase winding circuit, it is set to about 0.58 times the full-load current.

Will this overload relay fit my contactor?

Most overload relays are designed to mount directly on specific contactor sizes of the same brand and range. For other brands or sizes, a separate mounting kit or panel mounting is needed, so check the compatibility list.

Does it protect against single phasing?

Most modern thermal overload relays have differential (single phasing) sensitivity and trip faster when one phase is lost, which helps protect three-phase motors. For full phase failure and phase reversal protection, a phase monitoring relay is also recommended.

What is trip class 10 and class 20?

Trip class indicates the maximum time to trip from cold at 7.2 times the set current: class 10 trips within 10 seconds and class 20 within 20 seconds (IS/IEC 60947-4-1). Class 10 suits normal motors, while class 20 or 30 is used for heavy-starting loads like crushers and fans with large inertia.

What is the difference between manual and auto reset?

In manual reset, someone must press the reset button after a trip, while auto reset lets the relay reset itself once it cools. Manual reset is generally safer, since the motor will not restart unexpectedly.

No reviews yet