Schneider Schneider TeSys LADN Auxiliary Contact Block · TeSys D · 2NO · front mounting · LADN20 · LADN20
Rated current6 A
Ingress protectionIP20
Reference standardEN/IEC 60947-5-1
ColourDark grey
BrandSchneider
Brand SKULADN20
ELINE472H4CK69
Sold asPer pc
Depth42 mm
RangeTeSys · TeSys Deca
Width26 mm
Height48 mm
StandardsEN/IEC 60947-5-1 · GB/T 14048.5 · EN 50012 · UL 60947-5-1 · CSA C22.2 No 60947-5-1 · IEC 60335-1:Clause 30.2 · IEC 60335-2-40:Annex JJ · UL 60335-2-40:Annex JJ
Product nameTeSys Deca
Protection typeGG fuse 10 A
Non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact · 1.5 ms on energisation no overlap between NC and NO contact
Device short nameLADN
Mounting locationFront
Tightening torque1.7 N.m - with screwdriver flat Ø 6 mm · 1.7 N.m - with screwdriver Philips No 2 · 1.7 N.m - with screwdriver pozidriv No 2
Contacts operationInstantaneous
Operating altitude3000 m
Range compatibilityTeSys D CAD · TeSys D LC1D · TeSys F LC1F · TeSys F CR1F · TeSys Deca CAD · TeSys Deca LC1D
Protective treatmentTH conforming to IEC 60068
Insulation resistance> 10 MOhm
Mechanical durability30 Mcycles
Product certificationsCB Scheme · UL · CSA · CCC · EAC · UKCA
Connections - terminalsScrew clamp terminals 1 cable(s) 1…4 mm²flexible with cable end · Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end · Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end · Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end · Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end · Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable en
IP degree of protectionIP20 conforming to IEC 60529
Pole contact composition2 NO
Minimum switching current5 mA
Minimum switching voltage17 V
Product or component typeAuxiliary contact block
Irms rated making capacity140 A AC conforming to IEC 60947-5-1 · 250 A DC conforming to IEC 60947-5-1
Environmental characteristicNormal environment
Permissible short-time rating100 A 60 °C 1 s · 120 A 60 °C 500 ms · 140 A 60 °C 100 ms
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1 · 600 V conforming to UL · 600 V conforming to CSA
[Ie] rated operational current6 A at 120 V AC-15 · 1.04 A at 690 V AC-15 · 0.55 A at 125 V DC-13 · 0.1 A at 600 V DC-13
[Ue] rated operational voltage690 V AC 25...400 Hz
Ambient air temperature for storage-60…80 °C
Ambient air temperature for operation-5…60 °C
[Ith] conventional free air thermal current10 A (at 60 °C)
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.