Schneider Schneider Acti9 iEM3265 Energy Meter · 5 A · Class 0.5S active energy · A9MEM3265 · A9MEM3265
Poles3P+N (TPN)
Rated current5 A
Ingress protectionIP40 front panel:· IP20 body:
Reference standardBS EN 61557-12:2021
ColourWhite
BrandSchneider
Brand SKUA9MEM3265
ELINE2RC9P477F
Sold asPer pc
Depth69 mm
RangeActi9
Width90 mm
Height95 mm
StandardsBS EN 61557-12:2021 · IEC 61557-12:2021 · EN 61557-12:2021 · BS EN 61326-1 · IEC 61326-1 · EN 61326-1 · BS EN 62052-11:2020 · IEC 62052-11:2020 · EN 62052-11:2020 · BS EN 62053-21 · IEC 62053-21 · EN 62053-21 · BS EN 62052-22 · IEC 62053-22:2020 · EN 62052-22 · BS EN 62052-23 · IEC 62053-23:2020 · EN 62052-23 · BS EN 62052-31:2015 · IEC 62052-31:2015 · EN 62052-31:2015 · BS EN 61010-1:2010 · EN 61
input typeCurrent transformer 1 A or 5 A
9 mm pitches10
Display typeLCD display
tariff inputTariff (4)
Metering typeActive, reactive, apparent energy (signed, four quadrant)
Mounting modeClip-on
Rated voltage100…277 V · 173…480 V
Sampling rate32 samples/cycle
Accuracy classClass 0.5S active energy conforming to IEC 62053-22 · Class 0.5S active energy conforming to IEC 61557-12 · Class C active energy conforming to EN 50470-3
Market segmentBuildings small building cost management: billing: main incomer · Buildings small building cost management: billing: sub feeder · Buildings small building cost management: billing: panelboard · Buildings medium building cost management: billing: main incomer · Buildings medium building cost management: billing: sub feeder · Buildings medium building cost management: billing: panelboard · Buildings
Output voltage5...40 V DC@50 mA
Technology typeElectronic
Local signallingGreen indicator light: power ON · Yellow flashing LED: accuracy checking · alarm: overload
Mounting supportDIN rail
Number of inputs1 digital 0...5 V/11...40 V 24 V DC
Pollution degree2
range of productActi9 iEM3000
Device short nameiEM3265
Network frequency60 Hz · 50 Hz
Number of outputs1 digital (static)
Poles description3P · 1P + N · 3P + N
Relative humidity5…95 % at 50 °C
Compatibility codeIEM3265
Device applicationSub billing · Partial meter · Multi-tariff
Operating altitude< 3000 m
[In] rated current5 A · 1 A
Measurement current1…32767000 mA
Type of measurementActive and reactive energy · Active and reactive power · Current · Voltage
Overvoltage categoryIII
Maximum value measured99999999 MWh
Product certificationsCE conforming to IEC 61010-1 (safety) · CE conforming to EN 61557-12 (power monitor) · CE conforming to EN/IEC 61326-1 (EMC) · UKCA conforming to BS EN 61010-1 (safety) · UKCA conforming to BS EN 61557-12 (power monitor) · UKCA conforming to BS EN 61326-1 (EMC) · CULus conforming to UL 61010-1 (safety) · CULus conforming to EN 61010-1 (safety) · EAC conforming to EN 50470-3 (sub-meter) · RCM confo
Connections - terminalsCurrent circuit: screw terminals 6 mm² cable(s) · Voltage circuit: screw terminals 2.5 mm² cable(s)
IP degree of protectionIP40 front panel: conforming to IEC 60529 · IP20 body: conforming to IEC 60529
Product or component typeEnergy meter
Communication port supportScrew terminal block: RS485
Communication port protocolBACnet at 9.6, 19.2, 38.4, 57.6, 76.8 kbauds, insulation 4000 V
Ambient air temperature for storage-40…85 °C
Ambient air temperature for operation-25…70 °C - IEC
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.