Schneider Schneider TeSys Deca Auxiliary Contact Block · TeSys D · time delay auxiliary contact block · Off-delay · 10-180 s · Dark grey · LADR4 · LADR4
Rated current6 A
Ingress protectionIP20
Reference standardEN/IEC 60947-5-1
ColourDark grey
BrandSchneider
Brand SKULADR4
ELINE29PRR26K2
Sold asPer pc
Depth61 mm
RangeTeSys · TeSys Deca
Width44 mm
Height48 mm
StandardsEN/IEC 60947-5-1 · UL 60947-5-1 · CSA C22.2 No 60947-5-1 · GB/T 14048.5 · EN 50012 · IEC 60335-1:Clause 30.2 · IEC 60335-2-40:Annex JJ · UL 60335-2-40:Annex JJ
Time range10-180 s
Timer typeoff-delay
Product nameTeSys Deca
Protection typeGG fuse 10 A
Non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact · 1.5 ms on energisation no overlap between NC and NO contact
Time delay range10...180 s
Mounting locationFront
Tightening torque1.7 N.m - with screwdriver flat Ø 6 mm · 1.7 N.m - with screwdriver Philips No 2 · 1.7 N.m - with screwdriver pozidriv No 2
Contacts operationTime delay
Operating altitude3000 m
Range compatibilityTeSys Deca CAD · TeSys Deca LC1D · TeSys F LC1F · TeSys F CR1F
Protective treatmentTH conforming to IEC 60068
Insulation resistance> 10 MOhm
Mechanical durability5 Mcycles
Product certificationsIECEE CB Scheme · UL · CSA · CCC · EAC · UKCA
Connections - terminalsScrew clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end · Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end · Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid · Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end · Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end · Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid · Screw clamp terminals
IP degree of protectionIP20 conforming to IEC 60529
Pole contact composition1 NO + 1 NC
Minimum switching current5 mA
Minimum switching voltage17 V
Product or component typeTime delay auxiliary contact block
Irms rated making capacity140 A at <= 690 V AC conforming to IEC 60947-5-1 · 250 A at <= 690 V DC conforming to IEC 60947-5-1
Environmental characteristicNormal environment
Permissible short-time rating100 A 60 °C 1 s · 120 A 60 °C 500 ms · 140 A 60 °C 100 ms
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1 · 600 V conforming to UL 60947-5-1 · 600 V conforming to CSA C22.2 No 60947-5-1
[Ie] rated operational current6 A at 120 V AC-15 · 1.04 A at 690 V AC-15 · 0.55 A at 125 V DC-13 · 0.1 A at 600 V DC-13
[Ue] rated operational voltage690 V AC 25...400 Hz
Ambient air temperature for storage-60…80 °C
Ambient air temperature for operation-40…70 °C
[Ith] conventional free air thermal current10 A (at 60 °C)
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.